SPI9000 Inverter Unit FR4 – FR8 User Manual
MN04004003E
For more information visit: www.EatonElectrical.com A-1
April 2006
Appendix A — Fault Codes
When a fault is detected by the inverter control electronics, the drive is stopped and the
symbol F together with the ordinal number of the fault, the fault code and a short fault
description appear on the display. The fault can be reset with the RESET button on the
control keypad or via the I/O terminal. The faults are stored in the Fault History Menu M5,
which can be browsed. Table A-1 contains all the fault codes.
Table A-1: Fault Codes
Programmable.
Fault
Code Fault Possible Cause Solution
1 Overcurrent Inverter has detected too high a
current (>4xI
n
) in the motor cable:
sudden heavy load increase
short circuit in the motor
unsuitable motor
Check loading.
Check motor.
Check cables.
2 Overvoltage The DC-link voltage has exceeded
the limits defined in Table 1-4:
too short a deceleration time
high overvoltage spikes in supply
Set the deceleration time longer.
Add a brake chopper or brake
resistor.
3 Ground Fault
Current measurement has detected
that the sum of motor phase currents
is not zero.
insulation failure in cables or
motor
Check motor cable and motor.
5 Charging Switch The charging switch is open, when
the START command has been
given.
faulty operation
component failure
Reset the fault and restart.
Should the fault re-occur, contact
your Cutler-Hammer distributor.
6 Emergency stop Stop signal has been given from the
option board.
7 Saturation trip Various causes:
component failure
brake resistor short circuit or
overload
Cannot be reset from the keypad.
Switch off power.
DO NOT RE-CONNECT POWER!
Contact Eaton.
If this fault appears simultaneously
with Fault 1, check motor cables and
motor.
8 System fault component failure
faulty operation
Note: exceptional fault data record,
see Page 5-12.
Reset the fault and restart.
Should the fault reoccur, contact
your Cutler-Hammer distributor.